Tagpoint Controls LLC

Home  /  Capabilities

Capabilities & Sample Work

The standards behind every deliverable, from field tag to dashboard. Everything on this page is a reference or sample built to show how we work. Client projects stay confidential.

How to read this page: code excerpts, reference drawings and reference architectures are samples prepared to demonstrate standards and formats. None of them are client deliverables, and none of them describe a specific client’s system. Redacted excerpts of real work can be discussed under NDA.

TPC-C1 // Architecture stack

One tag model, five layers

Select a layer to see the standard we apply there. The same tag name travels from the field device to the report, which is why our drawings, code and screens agree.

L4

Reporting & enterprise

Dashboards · OEE · MES/ERP feeds

L3

Data & historian

SQL · MQTT · OPC UA

L2

Supervisory

HMI · SCADA · Alarming

L1

Control

PLC · DCS · Safety interface

L0

Field devices & I/O

Instruments · Drawings · Terminals

Level 4 · Reporting

Reports people actually open

Reports are built from the historian, never from screen scraping, so numbers match between shifts, sites and the ERP.

Sample excerpt

-- Shift OEE roll-up (sample)
SELECT line_id,
       shift_start,
       SUM(good_count) / NULLIF(SUM(total_count), 0) AS quality,
       SUM(run_sec)    / NULLIF(SUM(planned_sec), 0) AS availability
FROM   prod.shift_counts
WHERE  shift_start >= @from
GROUP BY line_id, shift_start;

Level 3 · Data

Structured data, not a tag dump

Data leaves the controller through a defined namespace and lands in a schema designed for the questions you will ask of it.

Sample excerpt

# Namespace (sample)
site01/packaging/line02/filler/state     "RUNNING"
site01/packaging/line02/filler/rate_bpm  412
site01/packaging/line02/filler/alarm     {"code":"F104","pri":2}

CREATE TABLE hist.analog (
  tag_id   INT        NOT NULL,
  ts       DATETIME2  NOT NULL,
  value    REAL,
  quality  SMALLINT,
  PRIMARY KEY (tag_id, ts)
);

Level 2 · Supervisory

Calm screens, honest alarms

HMI and SCADA screens follow high-performance principles: grey-scale by default, color only for abnormal states, and every alarm has a priority, a cause and an expected operator action.

Sample excerpt

Alarm classes (sample)
P1  Safety / critical   red     audible   ack + reason
P2  Process upset       amber   audible   ack
P3  Advisory            blue    silent    ack
P4  Maintenance         grey    silent    auto-clear
Rule: grey-scale by default; color = abnormal only

Level 1 · Control

Modular code with a state model

Every device type gets a data type and a reusable block with the same command, status, configuration, alarm and diagnostic structure. Sequences run as explicit state machines, so “why is it stuck?” has an answer on screen.

Sample excerpt

// UDT_Motor (sample structure)
UDT_Motor
 ├─ Cmd   Start, Stop, Reset, Mode (AUTO | MAN)
 ├─ Sts   Running, Faulted, Available, Interlocked
 ├─ Cfg   StartDelay_ms, FeedbackTimeout_ms
 ├─ Alm   FailToStart, FailToStop, Overload
 └─ Diag  RunHours, Starts, LastFaultCode
// States: IDLE → STARTING → RUNNING → STOPPING → FAULTED

Level 0 · Field

Tags, wires and terminals that agree

The I/O list is the single source of truth. Schematics, terminal plans, PLC tags and HMI labels are all generated from it, so a wire number on the drawing leads straight to the tag in the code.

Sample excerpt

Tag format (sample, ISA-5.1 based)
FIT-1203    Flow indicating transmitter · area 12 · loop 03
LSHH-2201   Level switch high-high · area 22 · loop 01
XV-1410     On/off valve · area 14 · loop 10
Wire 1203-FIT-01+   Terminal X12:31   PLC AI_1203_FIT

TPC-C2 // Standards

Three standards we never skip

Modular code

Reusable device blocks, a documented state model and consistent naming, so the tenth machine is faster than the first.

Structured I/O & drawings

The I/O list drives everything downstream. Drawings and code are generated from the same source and checked against each other.

SCADA → SQL pipelines

Data that arrives clean, timestamped and queryable, designed with your IT team rather than around them.

TPC-C3 // Reference drawings

Drawing formats we deliver

Reference drawings showing sheet types and drafting conventions. They are format samples, not client work. Select any drawing to enlarge it.

TPC-C4 // Reference architectures

How we would structure it

Illustrative architectures for common project types. These are design patterns, not descriptions of client systems.

RA-01 · Illustrative · not a client project

Packaging cell

Control

1 PLC, 3 VFDs on EtherNet/IP

Operator

12" HMI, 9 screens

Data

OEE counts to SQL

PackML-style state model, device UDT library, and shift reports built from the same counters the HMI displays.

RA-02 · Illustrative · not a client project

Batch process skid

Control

ISA-88 phases & recipes

Loops

Temperature cascade, flow ratio

Data

Batch records to historian

Equipment and control modules separated from recipe procedure, so new products need recipe changes, not code changes.

RA-03 · Illustrative · not a client project

Multi-site monitoring

Edge

Gateways with store-and-forward

Transport

MQTT Sparkplug B

Central

SCADA, SQL, dashboards

One namespace across sites, templated screens per asset type, and alarm routing by site and priority.

Next step

Want these standards on your project?

We can work to your existing standard or deliver ours as a starting template.